Custom ACSR EN 50182 NF C 34-125 Galvanized Steel Core Aluminum Conductor Factory, Exporters

Execution standard: BS EN 50182  (Old Standard: NF C 34-120)

Material: ACSR adopts Galvanized steel wire, AL1 aluminum.

ACSR is a versatile power transmission wire, where a robust steel core provides reliable structural backing and finely drawn aluminum wires form the outer layer for optimal conductivity.  Its impressive tolerance to extreme conditions makes it a trusted choice for high-voltage grids.

Product Description

ACSR Standard: EN 50182 (Old Standard: NF C 34 120)
Type: AL1/ST1A
Aluminum Conductor Steel Reinforced (ACSR)
Code Name Old Code Name Product structure Sectional Area Overall Diameter Nominal Breaking Load Linear Mass Maximum Resistance at 20℃ Modulus of elasticity Coefficient of linear expansion Direction of outside layer
Aluminium Wire Diameter & Stranding Galvanized steel Wire Diameter & Stranding Aluminium Galvanized steel Total
mm No. mm No. mm² mm² mm² mm kN kg/km Ω/km N/MM2 1/K /
28-AL1/9-ST1ACANNA 37.72.0092.00328.39.437.78.316.26151.51.0187880001.71x10-5S
38/AL1/22-ST1ACANNA 59.72.00122.00737.722.059.710.032.70276.10.7661035001.54x10-5S
48-AL1/28-ST1ACANNA 75.52.25122.25747.727.875.511.341.15349.40.60521035001.54x10-5S
59-AL1/34-ST1ACANNA 93.32.50122.50758.934.493.312.549.48431.40.49021035001.54x10-5Z
94-AL1/22-ST1ACANNA 116.22.00302.00794.222.0116.214.043.17432.50.3067755001.80x10-5S
119-AL1/28-ST1ACANNA 147.12.25302.257119.327.8147.115.854.03547.40.2423755001.80x10-5S
147-AL1/34-ST1ACANNA 181.62.50302.507147.334.4181.617.564.94675.80.1963755001.80x10-5S
185-AL1/43-ST1ACANNA 2282.80302.807184.743.1227.819.680.54847.70.1565755001.80x10-5S
234-AL1/55-ST1ACANNA 288.23.15303.157233.854.6288.322.198.581072.80.1236755001.80x10-5S
Type: AL1/ST6C
Aluminum Conductor Steel Reinforced (ACSR)
Code Name Old Code Name Product structure Sectional Area Overall Diameter Nominal Breaking Load Linear Mass Maximum Resistance at 20℃ Modulus of elasticity Coefficient of linear expansion Direction of outside layer
Aluminium Wire Diameter & Stranding Galvanized steel Wire Diameter & Stranding Aluminium Galvanized steel Total
mm No. mm No. mm² mm² mm² mm kN kg/km Ω/km N/MM2 1/K /
94-AL1/22-ST6CCROCUS 116.22.00302.00794.222.0116.214.049.32432.50.3067755001.80x10-5S
199-AL1/28-ST6CCROCUS 147.12.25302.257119.327.8147.115.861.83547.40.2423755001.80x10-5S
147-AL1/34-ST6CCROCUS 181.62.50302.507147.334.4181.617.574.22675.80.1963755001.80x10-5S
185-AL1/43-ST6CCROCUS 2282.80302.807184.743.1227.819.692.18847.70.1565755001.80x10-5S
234-AL1/55-ST6CCROCUS 2883.15303.157233.854.6288.322.1113.861072.80.1236755001.80x10-5S
222-AL1/76-ST6CCROCUS 2972.80362.2519221.775.5297.222.5147.221206.80.1307790001.69x10-5S
326-AL1/86-ST6CCROCUS 4123.60322.4019325.786.0411.726.4173.311576.10.0889720001.76x10-5Z
508-AL1/105-ST6CCROCUS 6123.13662.6519507.8104.8612.632.0231.552226.50.0570665001.83x10-5S
717-AL1/148-ST6CCROCUS 8653.72663.1519717.3148.1865.438.1319.113145.40.0403665001.83x10-5S
957-AL1/228-ST6CCROCUS 11852.80542.8037332.5227.8560.344.7480.754433.60.0302630001.83x10-5S
3.4766624.20.0
💡 Note:
1. The elastic coefficients and expansion coefficients listed in this table are applicable to France. The calculation of other conductor structure parameters shall refer to IEC61597.
2. The flow rate values listed in this table are applicable under the conditions of a frequency of 60HZ, a wind speed of 0.6m/S, sunlight exposure in France, an ambient temperature of 35℃, and a conductor temperature of 80℃. In case of special laying conditions, the flow rate values should be reduced if there is no convection Less than 30%.
Frequently Asked Questions (FAQ)
What is the EN 50182 standard for ACSR conductors?
EN 50182 is a European standard that specifies the characteristics and requirements for concentric lay stranded bare conductors for overhead lines, replacing older standards like NF C 34 120.
What is the difference between AL1/ST1A and AL1/ST6C?
These designations refer to the type of aluminum (AL1) and the grade/strength of the galvanized steel core (ST1A or ST6C). ST6C typically offers different mechanical properties, such as a higher breaking load for specific environmental conditions.
Why is steel used in the core of ACSR conductors?
The galvanized steel core provides the necessary mechanical strength and high breaking load required to support the conductor over long spans in overhead power transmission.
How does ambient temperature affect the ACSR conductor?
The electrical resistance is calculated at 20℃. High ambient temperatures or intense sunlight can increase the conductor's temperature, thereby increasing resistance and potentially reducing current-carrying capacity (flow rate).
What does "Direction of outside layer" signify?
The direction (S or Z) indicates the lay direction of the outermost wires. This is crucial for hardware compatibility and ensuring the conductor does not unwrap under tension.
Can these conductors be used in different environmental conditions?
Yes, though the table values are based on specific conditions (e.g., wind speed 0.6m/S). If laying conditions differ, such as lack of convection, the flow rate should be adjusted accordingly.