CE Certification AAC BS EN 50182 BS 215-1 All Aluminum Conductor Factories, Exporter

Execution standard: BS EN 50182  (Old Standard: BS 215-1)

Material: AAC adopts AL1 aluminum  material.

Product application: With a cost-effective profile compared to heavier conductor types, AAC aluminum stranded conductors offer an economical solution for large-scale electrical infrastructure projects without compromising basic performance.

AAC stands as a reliable all-aluminum conductor, crafted for optimal electrical performance with its pure aluminum composition.  Its lightweight design simplifies installation, while good corrosion resistance suits mild environmental conditions, making it a practical choice for distribution lines in less demanding settings.

Product Description

📋

AAC Standard: BS EN 50182 (Old Standard: BS 215-1)

Conductor Type: AL1

Aluminum Stranded Conductor (AAC) Specifications
Code Name Old Code Name Sectional Area Wire Diameter & Stranding Diameter of Conductor Nominal Breaking Load Linear Mass Max Resistance (20℃)
mm² mm No. mm kN kg/km Ω/km
23-AL1MIDGE23.32.0676.184.263.91.2449
27-AL1GNAT26.92.2176.634.8373.51.0643
37-AL1MOSQUITO36.92.5977.776.27101.00.7749
43-AL1LADYBIRD42.82.7978.377.28117.20.6678
53-AL1ANT52.83.1079.38.72144.70.5409
64-AL1FLY63.63.40710.210.49174.00.4497
74-AL1BLUEBOTTLE73.63.66710.9811.78201.70.3880
79-AL1EARWIG78.63.78711.3412.57215.10.3638
84-AL1GRASSHOPPER84.13.91711.7313.45230.20.3400
96-AL1CLEGG95.64.17712.5115.30261.80.2989
106-AL1WASP106.04.39713.1716.95290.10.2697
106-AL1BEETLE106.42.67198.0118.08292.70.2701
132-AL1BEE132.04.90714.721.12361.50.2165
158-AL1HORNET157.63.251916.2526.01433.70.1823
186-AL1CATERPILLAR185.93.531917.6529.75511.70.1546
213-AL1CHAFER213.23.781918.934.12586.70.1348
238-AL1SPIDER237.63.991919.9538.01653.70.1210
266-AL1COCKROACH265.74.221929.5442.52731.20.1081
323-AL1BUTTERFLY322.74.651932.5551.63887.90.0891
373-AL1MOTH373.15.00193559.691026.50.0770
372-AL1DRONE372.43.583725.0659.591027.20.0774
415-AL1CENTIPEDE415.23.783726.4666.431145.20.0695
486-AL1MAYBUG486.14.093728.6377.781340.80.0593
530-AL1SCORPION529.84.273729.8984.771461.40.0544
628-AL1CICADA628.34.653741.85100.541733.10.0459
Note: The outermost layer of the AAC conductor is twisted to the right (Z-lay).

Frequently Asked Questions (FAQ)

What is the standard for AAC Conductors?
The current international standard for Aluminum Stranded Conductor (AAC) is BS EN 50182, which supersedes the older BS 215-1 standard.
What does "Type AL1" signify?
AL1 refers to the specific grade of aluminum used in the stranded conductor, ensuring standard electrical conductivity and mechanical strength for overhead power lines.
Why do AAC conductors have insect code names?
In British standards, AAC conductors are traditionally assigned insect names (like Midge, Ant, Beetle, or Moth) to simplify identification of specific sizes and stranding configurations.
What is the significance of the "Z" twist?
The "Z" twist refers to the right-hand lay direction of the outermost wires. This specification is crucial for proper installation and compatibility with line hardware.
At what temperature is the maximum resistance measured?
The maximum electrical resistance for these conductors is calculated and measured at a standard reference temperature of 20°C.
How is the nominal breaking load determined?
The nominal breaking load (measured in kN) is calculated based on the sectional area and the minimum tensile strength of the AL1 aluminum wires used in the stranding.